- High performance fire survival coaxial cable
- Provides continued monitoring of evacuation routes in the event of fire
- London Underground Approved
Firetuf Coax is a high performance fire survival coax cable manufactured by Draka and designed to carry on functioning even in the event of a fire. This allows safe monitoring of evacuation routes without putting lives at risk.
Where video is carried the coax performs in a similar way to RG59 which is widely used in the CCTV sector. This allows continued monitoring of fire exits and evacuation routes in the event of a fire.
Where people and property come first the Draka Firetuf coax cable range provides the ideal solution.
Image representative of product style, product supplied may vary.
1/0.65mm solid plain copper conductor, PE/silicone rubber composite dielectric, woven glass tape, two plain copper wire braids, red Low Smoke Halogen Free sheath.
Flame Retardant: | IEC 60332-1-2 |
EN 60332-1-2 | |
IEC 60332-3-24C | |
EN60332-3-24C | |
BS 4066 Part 3 | |
Smoke Emission: | IEC 61034-2 |
EN 61034-2 | |
BS EN 50268-2 | |
Halogen Emission: | IEC 6075-1 |
EN 50267-2-1 | |
IEC 61034-2 | |
EN 50267-2-2 | |
LU 1-085 A2 |
PCWB - Plain Copper Wire Braid
Due to the unique size of FT Coax special BNC connectors have been designed as standard types do not fit.
Due to the unique size of FT Coax special BNC connectors have been designed as standard types do not fit.
BS 5839 Clause 26.2E | >2hrs @ 950°C |
BS 6387 | >3hrs @ 950°C |
IEC 60331-23 | >3hrs @ 750°C |
BS EN 50200 | >3hrs @ 950°C |
BS EN 50200:2000 | |
BS 8438-2:2003 | |
BS 8438-2 Class PH120 | 120 minutes |
BS 5839-1 2002 | +A2 2008 |
London Underground
LU 1-085-A2 fire safety performance of materials. Approved for use below ground without restriction.
Order by 4.30pm for delivery by